Product Description
Main feature:
1. Input signal: Thermoouple: E, K, S, B
Thermal resistance: Cu50, PT100
2. Accuracy: +/- 1.0% F. S, +/- 1 word
3. Control way: Two phase or time rate adjustment
4. Control output: Relay
5. Alarm function: High alarm function
6. Working power: AC110V, 220V, 380V, 50/60Hz
7. Outline dimension: 96 x 96 x 150mm
8. Install dimension: 92 x 92mm
 Â
 Main Technical IndexÂ
  1. InputÂ
    Refer to table B for Thermocouple (TC), Resistance Temperature Detector (RTD),Â
    Standard Current and Voltage signals.Â
  2. AccuracyÂ
    Measurement Accuracy: +/- 0.5%FS;Â
    Compensation error of cold terminal: +/- 2°C  (amend within -~50°C  by software);Â
    Resolution: 14bit;Â
    Sampling period: 0.5 Sec.Â
  3. DisplayÂ
    Process Value (PV), Setting Value (SV): -1999 ~ +9999Â
    Output, Alarm, Auto setting state indicated by: LEDÂ
  4. Control wayÂ
*(1)PID Control (including ON/OFF, position PID and continuous PID);Â
*(2)Auto Setting ControlÂ
5. Setting RangeÂ
    Setting Value (SV): Same range with PV;Â
    Proportional Band (P): 0~full range (ON/OFF Control when set to 0);Â
    Integration Time (I): 0~3600Sec (No integral action when set to 0);Â
    Derivative Time (D): 0~3600Sec (No derivative action when set to 0);Â
    Proportional Period: 1~100Sec;Â
    On-off control output hysteretic loop width: 1~100°C  (or other PV units).Â
6. Other ParametersÂ
*(1)Insulation resistance:  >50M(500VDC);Â
*(2)Insulation strength: 1500V AC/min;
*(3)Power consumption:  <10V;
*(4)Service environment: 0~50°C, 0~85RH, no corrosive gas;
*(5)Weight: ~ 0.5Kg (C900type).
Â
(1)Outline dimension  |
See the outline dimension picture  |
  |
(2)Control Mode  |
F:PID operation and auto calculating (reverse operation) Â |
D:PID operation and auto calculating(Forward operation) Â |
W: heating/cooling PID operation and auto calculating(cooling water)*1 Â |
A: heating/cooling PID operation and auto calculating(cooling wind)*1 Â |
|
(3)Input mode  |
Refer to Input Range Table  |
  |
(4)Range Code  |
Refer to Input Range Table  |
  |
(5)First control output(OUT1) (Heating side) Â |
M: Relay contact output  |
8: Current output(IC4-20mA) Â |
V: Voltage impulse output  |
G: Thyratron driving & triggering output  |
|
T: Thyratron output  |
  |
|
(6)Second controloutput (OUT2) (Cooling side)*2 Â |
No mark: when the control mode is F or D Â |
  |
M: Relay contact output  |
T: Thyratron output  |
|
V: Voltage impulse output  |
8: Current output(IC 4-20mA) Â |
|
 (7)First alarm (ALM1)   (8)Second alarm (ALM2)*2   |
N: no alarm  |
  |
A: Upper-limit deviation alarm  |
J: lower-limit input alarm  |
|
B: Lower-limit bias alarm  |
K: Standby upper-limit input alarm attached  |
|
C: Upper/lower limit bias alarm  |
L: Standby lower-limit input alarm attached  |
|
D: alarm in area  |
P: Heater line breakage alarm(CTL-6)*3 Â |
|
E: Standby upper-limit bias alarm attached  |
S: Heater line breakage alarm(CTL-12)*3 Â |
|
F: Standby lower-limit bias alarm attached  |
R: Control line breakage alarm *4 Â |
|
G: Standby upper/lower limit bias alarm  |
V: Upper-limit setting alarm  |
|
H: Upper-limit input value alarm  |
W: Lower-limit set value alarm  |
|
(9)Communication*5 Â |
N: No communication  |
  |
(10)Water-proof/dust-proof  |
N: no water-proof/dust-proof  |
  |
Â
Refer to Input Range Table Â
  |
Input type  |
Set range  |
Input type  |
Set range  |
|||
(TC) Thermocouple Input(TC) Â |
K Â |
0 to 1372°c(0 to 2502°F)  |
J Â |
0 to 1200°c(0 to 2192°F)  |
|||
R Â |
0 to 1769°c(0 to 3216°F)  |
S Â |
0 to 1769°c(0 to 3216°F)  |
||||
B Â |
0 to 1820°c(0 to 3308°F)  |
E Â |
0 to 1000°c(0 to 1832°F)  |
||||
N Â |
0 to 1300°c(0 to 2372°F)  |
T Â |
-199.9 to +400.0°c(-199.9 to +752.0°F)  |
||||
W5Re/W26Re  |
0 to 2320°c(0 to 4208)  |
PL Â |
0 to 1390°c(0 to 2534°F)  |
||||
L Â |
0 to 900°c(0 to 1652°F)  |
U Â |
-199.9 to +600.0°c(-199.9 to +999.9°F)  |
||||
RTD Input  |
Pt100 Ω( JIS/IEC )  |
-199.9 to +649.0°c (-199.9 to +999.9°F)  |
JPt100 Ω( JIS )  |
-199.9 to +649.0°c (-199.9 to +999.9°F)  |
|||
Voltage input  |
0 to 5V DC Â |
 1 to 5V DC  |
-1999 to +9999(programmable range) Â |
||||
Current input  |
0 to 20mADC Â |
4 to 20mADC Â Â |
-1999 to +9999(programmable range) Â |